ccHPWH

Product Info

What if there was a way to electrify a building’s DHW plant? Ice Air’s CCHPD-series cold climate heat pump domestic hot water heaters do just that! They capture the free energy in the environment and convert it to hot water.

The coefficient of performance (COP) ranges from 5.36 on the hottest days (115°F) to 2.43 on the coldest days (10°F). These units are certified to operate down to –13°F with a COP of 1.42 (1.43 times better than electric heat)… owning the title of cold climate operation.

There is no better way to electrify a building’s DHW plant than Ice Air’s CCHPD series.

Category: Air-Source Cold Climate Heat Pump Domestic Hot Water Heaters

Products: ccHPWH275-S, ccHPWH550-D, ccHPWH275-D, ccHPWH550-S

Thermostat Options

Ice Air - Product - HPWH - ccHPWH

Specifications

Model ccHPWH275-D ccHPWH550-D ccHPWH275-S ccHPWH550-S
Performance Specifications Input Power 208-230V/3Ph/60Hz 208-230V/3Ph/60Hz 208-230V/3Ph/60Hz 208-230V/3Ph/60Hz
Refrigerant Circuits 2 4 2 4
Refrigerant/ Quantity R410A (30.8 Lbs /
15.4 Lbs per circuit)
R410A (61.7 Lbs /
15.4 Lbs per circuit)
R410A (30.8 Lbs /
15.4 Lbs per circuit)
R410A (61.7 Lbs
/ 15.4 Lbs per circuit)
Max H/W Temperature 140°F 140°F 140°F 140°F
Dry Bulb Temperature (68°F)
Wet Bulb Temperature (59°F)
Inlet Water Temperature (59°F)
Outlet Water Temperature (131°F)
Heating Capacity (Btu/H) 306,000 637,300 310,800 647,400
Input Power(kW) 21.4 45.0 20.7 43.1
COP 4.2 4.15 4.4 4.4
Dry Bulb Temperature (45°F)
Wet Bulb Temperature (43°F)
Inlet Water Temperature (48°F)
Outlet Water Temperature (131°F)
Heating Capacity (Btu/H) 248,000 516,600 251,900 524,800
Input Power(kW) 22.0 45.9 21.4 44.6
COP 3.3 3.3 3.45 3.45
Dry Bulb Temperature (10°F)
Wet Bulb Temperature (7°F)
Inlet Water Temperature (43°F)
Outlet Water Temperature (131°F)
Heating Capacity (Btu/H) 160,300 333,800 162,800 339,100
Input Power(kW) 22.4 46.6 21.7 45.2
COP 2.1 2.1 2.2 2.2
FLA (A) 106.4 212.8 103.7 204.4
MCA (A) 134.6 254.4 134.6 254.4
MOCP (A) 175 300 175 300
Sound Level (dBA) ≤73 ≤75 ≤73 ≤75
Water Data Condenser Type Double Wall BPX Double Wall BPX Single Wall BPX Single Wall BPX
Water Side Pressure Loss (psig) 24.3 24.5 24.3 24.5
Rated Water Flow (GPM)
(DB/WB:45°F/43°F, Inlet/outlet: 104°F/113°F)
72.6 145.2 72.6 145.2
Single pass delta-T (F) (OA_temp=68°F, LWT=131°F) 10.37 10.80 10.53 11.00
Piping Position Rear Rear Rear Rear
Piping Sizes 2"(DN50) 3"(DN80) 2"(DN50) 3"(DN80)
Minimum Ambient Operating Temperature (°F) -13 -13 -13 -13
Overall Dimensions [L x W x H] (inches) 81 x 39 x 89 95 x 51 x 89 81 x 39 x 89 95 x 51 x 89
Net Weight (Lbs) 1,555 2,950 1,555 2,950