RS16 – Replacement PTAC – Type 16 Series

Product Info

Ice Air RS16 Series Replacement and Retrofit units are high energy efficiency PTACs. Designed from the ground up for ultra-high efficiency, they incorporate advanced LEEDs features in a durable and user friendly package.

Category: Replacement PTAC

Replaces: American Air Filter (AAF) – Type 16; American Standard – Type 45; McQuay – Type 16, PNES; Singer – ENR; Islandaire – 16; Retroaire – RC/RH10; Remington – Type 16

See all PTAC Products PTAC Accessories Thermostat Options

Ice Air - Product - PTAC - RS16 - Replacement - Type 16 Series

Specifications

SERIES MODEL # 5RS1613 8RS1613 8RS1618
Cooling Capacity1 (BTU/h) 11,500 12,100 15,900
EER 8.9 9.0 8.1
Heating Capacity – Hot Water2 (BTU/h) 15,500 15,500 15,500
Heating Capacity – Steam3 (BTU/h) 18,700 18,700 18,700
Electric Heating MAX (kW) 1.5 4.3 4.3
Voltage 115 208/230 208/230
Amperage 11.2 6.5 9.4
Watts 1,292 1,344 1,963
Airflow AC High Speed (CFM) 430 430 450
Airflow AC Low Speed (CFM) 350 350 360
Airflow Heat (CFM) 240 240 250
Airflow Outside (CFM) 60 60 60
Weight Net/Ships (lbs) 121/138 121/138 141/157
SPECIFICATION NOTES:
1. Cooling mode performance ratings are in compliance with AHRI standard 310/380 and CSA standard 744.
2. BTUH @ 200 °F. E.W.T.; 65 °F. E.A.T. & 2 G.P.M. flow rate
3. BTUH @ 2 PSIG STEAM & 65°F. E.A.T.
4. Performance data based on R32 green refrigerant.


IMPORTANT: Additional voltages and alternate electric heat and heat pump options are available. For performance data and other available options please consult factory. Accessories are optional. Deviations from standard accessories may affect performance; louver requires 70% free area per original OEM specification; room enclosures must provide sufficient return air, free flowing supply air and must be properly sealed to prevent air recirculation; any non-standard components or accessories must be reviewed and approved by Ice Air or approved distributor.