RSMK – Replacement PTAC – Type K, EK Series

Product Info

ICE AIRs RSMK Series Replacement and Retrofit units are high energy efficiency PTACs. Designed from the ground up for ultra-high efficiency, they incorporate advanced LEEDs features in a durable and user-friendly package.

Category: Replacement PTAC

Replaces: Singer – K, EK; Remington – K, EK; McQuay – K, EK, RK; Ice-Cap – RSK/K; RSMK

See all PTAC Products PTAC Accessories Thermostat Options

Ice Air - Product - PTAC - RSMK - Replacement - Type K, EK Series

Specifications

SERIES MODEL # 5RSMK09 5RSMK13 8RSMK09 8RSMK13 8RSMK16 7RSMK09 7RSMK13
Cooling Capacity1 8,550 11,750 8,550 11,500 13,500 8,550 11,750
EER 9.1 8.4 9.1 8.5 8.05 9.1 8.4
Heating Capacity (Hot Water)2 16,500 16,500 16,500 16,500 19,400 16,500 16,500
Heating Capacity (Steam)3 18,700 18,700 18,700 18,700 20,000 18,700 18,700
Electric Heating Max. (KW) 1.5 1.5 1.5 4.3 4.3 3.5 3.5
Voltage 115 115 208/230 208/230 208/230 277 277
Amperage 8.2 12.2 4.5 6.5 8.1 3.4 5.0
Watts 940 1,399 940 1,353 1,677 940 1,399
CFM Room Air High 370 370 370 430 430 370 370
CFM Room Air Low 350 350 350 370 370 350 350
Specification Notes:
1. BTUH @ 80°F. DB / 67°F. WB INDOORS; 95°F. DB OUTDOORS.
2. BTUH @ 200°F. E.W.T.; 65°F. E.A.T. & 2 G.P.M. FLOW RATE.
3. BTUH @ 2 PSIG STEAM & 65°F. E.A.T.