Specifications

SERIES MODEL # 5RSNU07-H 5RSNU09-H 5RSNU13-H 8RSNU09-H 8RSNU13-H 8RSNU18-H
Cooling Capacity1 (BTU/h) 8,300 9,000 11,500 9,600 11,900 16,600
Sensible Cooling Capacity1 (BTU/h) 6,600 7,200 9,200 7,700 9,500 11,600
EER 11.6 11.4 10.6 11.2 11.0 9.5
Heating Capacity2 (BTU/h) 7,500 8,700 11,400 9,300 11,600 16,000
COP 3.4 3.8 3.5 3.8 3.7 3.3
Voltage 115 115 115 208/230 208/230 208/230
Electric Heater Power3 (kW) 1.5 1.5 1.5 3.0 | 3.5 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3
Electric Heater Current3 (A) 13 13 13 14.4 | 16.8 14.4 | 16.8 | 20.7 14.4 | 16.8 | 20.7
Cooling Mode Current (A) 6.2 6.9 9.4 4.1 5.2 8.4
Cooling Mode Power (W) 716 789 1,085 857 1,082 1,747
MCA (without Electric Heat) 8.5 9.6 12.1 5.3 6.6 9.0
MOCP (without Electric Heat) 15 15 15 15 15 15
MCA (with Electric Heat) 16.7 17.2 17.2 18.5 | 21.5 18.5 | 21.5 | 26.3 18.6 | 21.6 | 26.5
MOCP (with Electric Heat) 20 20 20 20 | 25 20 | 25 | 30 20 | 25 | 30
Airflow AC High Speed (CFM) 380 380 400 380 400 540
Airflow AC Low Speed (CFM) 300 300 350 300 350 450
Airflow Outside (CFM) 60 60 60 60 60 60
Airflow Extra Outside (CFM) 110 110 110 110 110 110
Weight Net/Ship (lbs) 130/141 134/145 134/145 134/145 134/145 137/148
SPECIFICATION NOTES:
1. Cooling mode performance ratings are in compliance with AHRI standard 310/380 and CSA standard 744.
2. Heating mode performance ratings are in compliance with AHRI standard 310/380 and CSA standard 744.
3. Heat pump operation disabled below 38 °F (± 3 °F)
4. Optional can be motorized.
5. Performance data based on R32 green refrigerant.


IMPORTANT: Additional voltages and alternate electric heat and heat pump options are available. For performance data and other available options please consult factory. Accessories are optional. Deviations from standard accessories may affect performance; louver requires 70% free area per original OEM specification; room enclosures must provide sufficient return air, free flowing supply air and must be properly sealed to prevent air recirculation; any non-standard components or accessories must be reviewed and approved by Ice Air or approved distributor.