RSXC – New Construction/Replacement PTHP – Cold Climate Heat Pump

Product Info

Ice Air’s breakthrough cold climate technology is a paradigm shift. It allows Packaged Terminal Heat Pumps (PTHPs) to efficiently provide space heating down to -5°F and below. And our advanced Variable Refrigerant Flow (VRF) technology ensures that your unit is pinpointing the exact amount of heating or cooling required for the desired room conditions. Efficient, sustainable, heat pumps designed for cold climates are finally a reality.

Category: New Construction
Products: RSXC09, RSXC13, RSXC18

See all PTHP Products PTAC Accessories Thermostat Options

Ice Air - Product - PTAC - RSXC - New Construction - Cold Climate Heat Pump

Specifications MasterSpec

Series Model # RSXC09 RSXC13 RSXC18
Cooling Capacity (Btu/hr)1 9,200 12,500 16,300
Sensible Capacity (Btu/hr)1 7,200 8,800 11,200
Cooling Capacity Range (Btu/hr) 6,300 – 11,800 6,500 – 14,900 7,300 – 18,000
EER 12.1 11.1 10.0
Heating Capacity (Btu/hr)2 10,200 12,000 17,300
Heating Capacity Range (Btu/hr) 5,200 – 12,600 5,600 – 14,200 9,500 – 18,700
COP 3.6 3.1 3.0
HSPF 9.6 9.5 9.0
Voltage 115 208 115 208 208
Electric Heater (kW)3 1.5 3.0 | 3.5 1.5 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3
Electric Heater (A)3 13 14.4 | 16.8 13 14.4 | 16.8 | 20.7 14.4 | 16.8 | 20.7
Current in Cooling Operation (Amps) 6.6 3.7 9.8 5.4 7.8
Power in Cooling Operation (Watts) 760 1,126 1,630
Current in Heating Operation (Amps) 7.2 4.0 9.9 5.5 8.1
Power in Heating Operation (Watts) 830 1,134 1,690
MCA (without Electric Heat) 11.7 5.9 12.6 8.5 10.4
MOCP (without Electric Heat) 20 15 20 15 15
MCA (with Electric Heat) 17.0 18.4 | 21.5 17.0 18.4 | 21.5 | 26.4 18.4 | 21.5 | 26.4
MOCP (with Electric Heat) 20 20 | 25 20 20 | 25 | 30 20 | 25 | 30
Evaporator Motor Nominal HP 1/25 1/25 1/25 1/25 1/25
Airflow (CFM) 380 400 480
Outside Air (CFM) 60 60 60
Weights (lbs.) 127 134 151
  Low Ambient Performance
Heating Capacity @ 10°F 6,600 7,700 11,600
COP @ 10°F 2.2 2.14 2.02
Heating Capacity @ 5°F 6,100 6,900 10,600
COP @ 5°F 1.98 1.91 1.93
Heating Capacity @ -5°F 5,500 6,400 8,100
COP @ -5°F 1.74 1.62 1.6
Specification Notes:
1. Rated performances in cooling mode @80°F/67°F DB/WB Indoors and 95°F/75°F DB/WB Ambient
2. Rated performances in heating mode @ 70°F/60°F DB/WB Indoors and 47°F/43°F DB/WB Ambient
3. If the electric heat option is selected, the heat pump operation is disabled and electric heat enabled below -5°F (+/- 3 °F).
4. Units without electric heat will operate below -5°F with derated performance. Performance below -5°F has not been certified.
5. Electric heat is recommended in markets that may experience ambient temperatures below -5°F.