RSXC – New Construction/Replacement PTHP – Cold Climate Heat Pump

Product Info

Ice Air’s breakthrough cold climate technology is a paradigm shift. It allows Packaged Terminal Heat Pumps (PTHPs) to efficiently provide space heating down to -5°F and below. And our advanced Variable Refrigerant Flow (VRF) technology ensures that your unit is pinpointing the exact amount of heating or cooling required for the desired room conditions. Efficient, sustainable, heat pumps designed for cold climates are finally a reality.

Category: New Construction
Products: RSXC09, RSXC13, RSXC18

See all PTHP Products PTAC Accessories Thermostat Options

Ice Air - Product - PTAC - RSXC - New Construction - Cold Climate Heat Pump

Specifications

SERIES MODEL # 8RSXC09 8RSXC13 8RSXC18
Cooling Capacity1 (BTU/h) 9,200 12,500 16,300
Cooling Capacity Range (BTU/h) 6,300 – 11,800 6,500 – 14,900 7,300 – 18,000
EER1 12.1 11.1 10.0
Heating Capacity2 (BTU/h) 10,300 13,700 17,900
Heating Capacity Range (BTU/h) 8,700 – 12,600 9,000 – 14,700 10,900 – 19,300
COP2 4.1 3.7 3.0
HSPF2 9.6 9.5 9.0
Voltage 208 208 208
Electric Heater Power3 (kW) 3.0 | 3.5 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3
Electric Heater Current3 (A) 14.4 | 16.8 14.4 | 16.8 | 20.7 14.4 | 16.8 | 20.7
Cooling Mode Current (A) 3.7 5.4 7.8
Cooling Mode Power (W) 760 1,126 1,630
Heating Mode Current (A) 3.5 5.2 8.4
Heating Mode Power (W) 737 1,086 1,750
MCA (without Electric Heat) 7.9 9.9 12.9
MOCP (without Electric Heat) 15 15 15
MCA (with Electric Heat) 18.4 | 21.5 18.4 | 21.5 | 26.4 18.4 | 21.5 | 26.4
MOCP (with Electric Heat) 20 | 25 20 | 25 | 30 20 | 25 | 30
Evaporator Motor Nominal HP 1/25 1/25 1/25
Airflow (CFM) 380 400 480
Airflow Outside (CFM) 60 60 60
Weights (lbs) 127 134 151
  Low Ambient Performance
Heating Capacity @ 10°F 6,600 7,700 11,600
COP @ 10°F 2.20 2.14 2.02
Heating Capacity @ 5°F 6,100 6,900 10,600
COP @ 5°F 1.98 1.91 1.93
Heating Capacity @ -5°F 5,500 6,400 8,100
COP @ -5°F 1.74 1.62 1.60
SPECIFICATION NOTES:
1. Cooling mode performance ratings are in compliance with AHRI Standard 310/380 and CSA Standard 744.
2. Heating mode performance ratings are in compliance with AHRI Standard 310/380 and CSA Standard 744.
3. (OPTIONAL) If back-up electric heat is required, customer has choice of manual trigger switch OR automatic changeover at -5°F (±3°F) with manual switch override.
4. Units without electric heat will operate below -5°F with derated performance. Performance below -5°F has not been certified.
5. Electric heat is recommended in markets that may experience ambient temperatures below -5°F
6. Performance data based on R32 green refrigerant.


IMPORTANT: Additional voltages and alternate electric heat and heat pump options are available. For performance data and other available options please consult factory.